Ventilation Planning

[sketch] Ventilation Planning - gym window roof fan

The models screenshotted here exist as a sketchup file in my account. Can't attach bc too big, but can hand off to anyone directly. (~LP)


Overview

Shows basement below, and rough outline of gym space.
Weird curved thing up top is the manifold/cowl for the existing large fan above gym.LP-vent-basement-proposal-overview.jpeg

LP-vent-basement-proposal-focussed.jpeg

Basic idea is three channels.

  1. Toxic out via existing roof pipe (all rigid pipe, leak tested on regular basis, not "hot swappable", maybe lower CFM.
  2. Coffee & general air out via existing fan manifold, maybe draws from woodshop, higher CFM.
  3. Fresh air in from gym window, higher CFM, with exit in center of space

LP-vent-basement-proposal-detail.png

A) Optional add-on for gym, variable speed fresh air intake biscuit fan
B) Clean air intake via 4" hole in floor
C) Coffee+ high CFM output via another 4" hole in floor, and then through gym fan manifold, but probably just using it as a pathway, not relying on gym fan itself
D) Toxic out

We have exactly enough straight conduit to do this.
We don't have elbows, Ts, blast gates
Not sure how and what fans are used for different lines

Concerns have been expressed about 4" round being enough.
Maybe possible to bump to 6", maaaaaybe 8", but gets trickier re: finding cheap blowers, and becomes more obtrusive to gym space. Not my area of expertise, but I think 4" with proper blowers is workable.

Apparently "pulling" air is more efficient, so intake blower would be in basement, non-toxic outflow could be mounted in fan manifold, and toxic out we'd probably eat the inefficiency vs mounting fan on roof exposed to elements.

Gym coordination

Sent this mockup to gym for input 9/12/26

RC-gym-ventilation-panel.jpeg

RC-basement-ventilation-gym-details.jpeg

[sketch] Ventilation planning - gym window 2x duct

The sketch here was objected to by at least some gym folks because it interferes with space behind squat rack.

To avoid:

We can maybe route through the exiting vertical square duct, but then exit from the side, to a panel mounted in upper gym window vs lower.

The big picture

Having 2 outflows will I guess create negative pressure in space, and pull air from 1st FL

Measurements and Supplies

Roof pipe being used for roasting venting

76 ID
88.5 OD

Candidate blower for MVP exhaust: https://www.grainger.com/product/DAYTON-Blower-3-7-8-in-Wheel-Dia-42NL22

[sketch] MVP ventilation

Rear - Outflow

50 CFM outflow from rear via dedicated $100 blower.

It turns out a more standard blower is probably not ideal for the high static pressure of a 3" pipe run.

A radon fan may be more suitable, at a slight increase in purchase cost and running cost.

Main radon fan manufacturers appear to be RadonAway & Fantech, some options:

Leaning towards Festa AMG Triumph ECS

Table of fan comparisons

RC-basement-fan-01a.jpeg

RC-basement-fan-02a.jpeg

RC-basement-fan-03a.jpeg

RC-basement-fan-04a.jpeg

Exhaust fan options: 3" iron pipe, ~20 ft vertical, 2–3 × 45°, open top

Annual cost = max rated watts × 8,760 h × $0.29/kWh (Con Ed residential, 2026). Commercial accounts run ~15–25% lower. "Est. on pipe" = estimated operating point on this run. "—" = not published / not found.

Rn4EC-3 rated points (3" duct): 100%: 36 CFM @ 4.5" (146 W), 210 CFM @ 0.2" (173 W). 80%: 29 CFM @ 3.19" (88 W), 180 CFM @ 0.2" (126 W). 60%: 20 CFM @ 1.75" (40 W), 130 CFM @ 0.2" (57 W).

Notes for coffee roasting exhaust (1 kg electric, tented):
- Measure air temp at the fan inlet during the darkest roast. Above ~104°F, only the 1TDV2 is rated for it.
- Oil residue condenses as smoke cools. Scroll blowers can be opened and cleaned; radon fans are sealed and effectively consumable in this use.
- Use a washable mesh/baffle grease filter at the tent outlet.
- Fan at the top (pulling) keeps the iron pipe under suction, so leaks in the ceiling space draw air in rather than leaking smoke out.
- Add a cleanout/drip cup at the bottom of the vertical run.
- Est. on-pipe figures are rough calculations, not measurements.


Reduces roasting impact, improves CO2 and VOC reduction.

Front - Inflow/Outflow switchable

Big dust collection blower near hatch.
With longer hoses on in/out, could swap between inflow/outfow.
Hose can hook on to 1/2 opened hatch door.
Would be better with ducting, but routing past electrical panel and lift would be difficult.

Inflow

Set up for inflow, would work in tandem with rear exhaust.

Outflow

Set up for exhaust, could make the front area suitable for painting/staining.
Would benefit from cordoning off area to avoid drafts to upstairs or rest of basement.
Probably doesn't need to be entirely enclosed to help.

Next Steps

To improve outflow from rear, add additional exhaust:

To improve incoming airflow from front, add additional incoming ducting: